+91-8755475716 WhatsApp Us Send EnquiryStatic electricity is easy to ignore until it costs money. A technician walks across a dry floor in January, touches a circuit board, and a component fails weeks later in the field. A server room loses a line card after someone pulls a trolley across it. In Delhi, where winter air gets very dry, these problems get worse between November and February. An ESD floor gives static a controlled path to earth before it can reach your equipment.
These two words get mixed up a lot, and choosing the wrong one can mean a floor that fails your audit.
| Type | Typical resistance to ground | Where it is used |
|---|---|---|
| Conductive | below 10⁶ ohms | Areas with explosives or flammable vapours, some OTs |
| Static dissipative | 10⁶ to 10⁹ ohms | Electronics assembly, repair benches, labs, server rooms |
Most electronics work falls under static dissipative, in line with ESD programmes based on ANSI/ESD S20.20 or IEC 61340-5-1. Your ESD coordinator or equipment supplier should tell you the range to design for, and we build the floor to match it.
An ESD floor is a small electrical system, not just a coating.
If any step is skipped, particularly the earthing and testing, you have an expensive floor that only looks like an ESD floor.
Staff also need ESD footwear or heel grounders for the floor to protect anything. Ordinary rubber-soled shoes insulate a person from the floor. We say this at every site visit because it is the most common reason an ESD programme doesn't work.
Server rooms and hospitals can't simply be switched off. We plan the work in sections, protect running equipment from dust, and work at night where needed. For data centres, sub-floor work under raised floors is scheduled around your change windows.
Test it at handover, then periodically as part of your ESD programme. Many facilities test every six to twelve months, and after any major floor repair.
No. Wax and many polishes leave an insulating film that ruins the floor's performance. Use cleaners recommended for ESD floors.
Sometimes. If the existing floor is sound, we can grind it, lay the copper grid and conductive primer, and apply an ESD finish on top.
Call +91-8755475716 or fill in the form below to discuss your room in Delhi. More details are on our antistatic ESD flooring page.